80GHz Radar Level Meter

80GHz Radar Level Meter

Product description

MRD110 series radar level meter is an 80G FM radar type level measuring instrument with a measuring distance of up to 30 meters. The antenna is further optimized, and the new fast microprocessor can perform higher-speed signal analysis and processing, so that the instrument can be used for the measurement of environmental liquids such as high temperature and high pressure.

Product principle

The general principle of the FM continuous wave radar level meter is that the radar emits electromagnetic waves on the top of the tank, and the electromagnetic waves are received by the radar after being reflected by the medium. The frequency difference δf between the received signal and the transmitted signal is proportional to the distance R from the medium surface. : R= C (speed) * δ f (frequency difference) /2/ K (frequency modulation slope). Because the speed of light C and the frequency modulation slope K are known, the frequency difference δf is estimated, and the distance R from the material surface at the location where the radar is installed can be obtained. Then, through the known total height of the tank, subtract the spatial distance from the radar to the material surface (Abbreviated as empty height), get the height of the material level.


Features

Millimeter wave radar, the measurement accuracy can reach up to ±2mm, and the minimum blind area of measurement is 0.05m

Smaller antenna size to meet the measurement of more working conditions

Various lens antennas, smaller launch angle, more concentrated energy, stronger echo signal, higher reliability than other radar products under the same industrial and mining conditions

With stronger penetration, it can also be used normally under the condition of adhesion and condensation

Larger dynamic signal range for more stable measurements on low dielectric constant media

A variety of measurement modes, the radar response time is less than 1s in the fast measurement mode

 

Product parameters

Measuring medium: liquid

Measuring range: 0.05m~30m

Process connection: G1½ A/1½NPT thread/flange≥DN50

Process temperature: -4080

Process pressure: -0.10.3MPa

Accuracy: ±2mm

Protection class: IP67

Frequency range: 123GHz

Power supply: two-wire system (DC24V)/four-wire system (DC12V~24V)/four-wire system (AC220V)

Explosion-proof grade: Exia IIC T6 Ga / Exd IIC T6 Gb

Housing: Aluminum/Plastic/Stainless Steel

Signal output: 2-wire 4...20mA/HART protocol/4-wire 4...20mA/RS485 Modbus

 

 

Dimensions

Installation requirements

When installing the instrument, avoid installing it above the feeding port, and try to avoid various objects that affect the signal, such as stirring paddles, etc.

Under extremely complex working conditions, the instrument can work normally without any obstacles within a radius of 20cm with the radar installation point as the center.


It cannot be installed above the feed inlet, and there can be no obstacles under the meter.

Under extremely complex working conditions, the instrument can work normally without any obstacles within a radius of 20cm with the radar installation point as the center.


Electrical connections

Supply voltage:

(4~20) mA/HART (two-wire): The power supply and the output current signal share a two-core shielded cable. Refer to the technical data for the specific supply voltage range.

(4~20) mA (four/six-wire): The power supply needs to be powered separately, and a four-core shielded cable is used for the power supply and the current signal (the current signal and the RS485 interface can be output at the same time, and a six-core cable is required for the output at the same time). Shielded cable).

RS485/Modbus: The power supply needs to be powered separately, and a four-core shielded cable is used for the power supply and digital (current signal and RS485 interface can be output at the same time, and a six-core shielded cable is required for output at the same time).

Wiring

The wiring diagram of 24V two-wire is as follows:

Side shows, 2-wire wiring diagram as follows:

The 4-wire wiring diagram is as follows:

Safety Guidance

Please observe the requirements of the local electrical installation regulations!

Follow local regulations for personnel health and safety. All operations on the electrical components of the instrument must be done by formally trained professionals.

Please check the meter's nameplate to ensure that the product specifications meet your requirements. Make sure that the power supply voltage is consistent with the requirements on the meter's nameplate.

Protection class

This instrument fully meets the requirements of protection class IP66/67, please ensure the waterproofness of the cable gland. As shown

How to make sure your installation meets IP67 requirements:

Make sure the sealing head is not damaged.

Make sure the cable is not damaged.

Make sure that the cables used meet the electrical connection specifications.

Bend the cable down before entering the electrical interface to ensure that water does not flow into the housing, see ①

Please tighten the cable gland, see ②

Please plug the unused electrical connections with blind plugs, see ③ 


Parameter

Process connection: flange/material PP, PTFE, stainless steel, stainless steel + PTFE flange

Antenna Profile: PTFE

Housing: Cast Aluminum / Stainless Steel / Plastic ABS

Seal between housing and housing cover: Silicone rubber

Housing Window: Polycarbonate

Ground Terminal: Stainless Steel

Supply voltage

Two-wire (single/dual): (15-28) V DC

Power consumption: max 80mA DC24V/ 2W

Allowable ripple <100Hz Uss < lV

                         (100~100K) Hz Uss < l0mV

Four-wire system (dual cavity): (198~242)V AC

                                                  110V AC

Cable parameters

Cable entry/plug: 1 M20x1.5 cable entry

                            1 blind plug M20×1.5

Terminal block: conductor cross section 2.5mm²

Output parameters

Output signal: (4~20) mA /HART protocol

Resolution: 1mm

Fault signal: current output unchanged; 20. 5mA; 22mA; 3.9mA

Integration time: (0~20)s, adjustable

Blind area: 0.1m/0.2m/0.3m

Maximum measuring distance: 150 meters

Measurement interval: about 1 second (depending on parameter settings)

Adjustment time: about 1 second (depending on parameter settings)

Working storage and transportation temperature: (-40~80) ℃

Relative humidity: ˂ 95%

Pressure: Max. 2.5MPa

Shock resistance: mechanical vibration 10m/s², (10~150)Hz


 

 