26G Radar Level Meter
- Product No.:MRD9002
Product description
MRD9002 series 26G high frequency radar level meter, the measurement distance can reach 80 meters. The antenna is further optimized, and the new fast microprocessor can perform higher-speed signal analysis and processing, so that the instrument can be used for the measurement of various strong corrosive liquids.
Product principle
The radar level antenna emits narrow microwave pulses, which are transmitted downward through the antenna. After the microwave touches the surface of the measured medium, it is reflected and received by the antenna system again, and the signal is transmitted to the electronic circuit part and automatically converted into a level signal (because the microwave propagation speed is extremely fast, the electromagnetic wave reaches the target and is reflected to the receiver. The time taken is almost instantaneous).
A: Range setting, B: Low position adjustment, C: High position adjustment, D: Blind zone range
The reference surface for measurement is: the bottom surface of the thread or the sealing surface of the flange.
Note: When using radar level timing, make sure that the highest material level cannot enter the measurement blind area (the area shown in D in the figure).
Features
The antenna is small, easy to install; non-contact radar, no wear, and no pollution.
Almost unaffected by corrosion, foam; almost unaffected by atmospheric water vapor, temperature, and pressure changes.
Severe dust environment has little effect on the work of high frequency level gauge.
Shorter wavelengths, better reflection on inclined solid surfaces.
The beam angle is small and the energy is concentrated, which enhances the echo capability and helps to avoid interference.
The measurement blind area is smaller, and good results are also obtained for the measurement of small tanks.
High signal-to-noise ratio for better performance even under fluctuating conditions.
At high frequencies, it is a better choice for measuring solids and low dielectric constant media.
Product Specifications
Application: temperature-resistant, pressure-resistant, slightly corrosive liquids
Measuring range: 30 meters
Process connection: thread, flange
Process temperature: -40 to 130°C (standard type) / -40 to 250°C (high temperature type)
Process pressure: -0.1~4.0MPa
Accuracy: ±3mm
Protection class: IP67
Frequency range: 26GHz
Power supply: two-wire system (DC24V)/four-wire system (DC24V/AC220V)
Explosion-proof grade: Exia IIC T6 Ga / Exd IIC T6 Gb
Housing: Aluminum Single Chamber / Aluminum Double Chamber / Plastic / Stainless Steel Single Chamber
Signal output: 4...20mA/HART (two-wire/four-wire) / RS485 Modbus
Dimension
Technical parameter
Process connection |
Thread G1½” A / Thread 1½” NPT / Flange |
||
Antenna material |
stainless steel / PTFE |
||
Shell |
Seal between housing and housing cover |
Silicone Rubber |
|
Shell window |
Polycarbonate |
||
Ground terminal |
Stainless steel |
||
Supply voltage |
two-wire |
Standard |
(16~26) V DC |
Intrinsically Safe |
(21. 6~26. 4) V DC |
||
Power consumption |
max 22. 5mA / 1W |
||
Ripple allowed |
|||
Flameproof |
- <100Hz |
Uss < lV |
|
- (100~100K) Hz |
Uss < l0mV |
||
(22. 8~26. 4) V DC |
two-wire |
||
(198~242) V AC |
four-wire / 110V AC four-wire |
||
Cable |
Cable entry/plug |
1 M20x1.5 cable entry |
|
1 blind plug M20x1.5 |
|||
Terminals |
Conductor cross section 2.5mm² |
||
Output parameters |
Output signal |
(4~2 0) mA |
|
Protocol |
HART |
||
Resolution |
1. 6μA |
||
Fault signal |
Current output remains unchanged |
||
20. 5mA |
|||
22mA; |
|||
3.9mA |
|||
Integration time |
(0~36)s,adjustable |
||
Blind spot |
Antenna end |
||
Maximum measuring distance |
MRD9001 |
10米 (liquid) |
|
MRD9002 |
30米 (liquid) |
||
MRD9002T |
20米 (liquid) |
||
MRD9003 |
70米 (solid) |
||
MRD9004 |
80米 (solid) |
||
MRD9005 |
30米 (solid) |
||
MRD9006 |
20米 (liquid) |
||
Microwave frequency |
26GHz |
||
Communication Interface |
HART Protocol |
||
Measurement interval |
About 1 second (depending on parameter settings) |
||
Adjust time |
About 1 second (depending on parameter settings) |
||
Display resolution |
1mm |
||
Operating Storage and Shipping Temperatures |
(-40~100) ℃ |
||
Process temperature (temperature of the antenna section) |
MRD9001 |
(-40~130)℃ |
|
MRD9002 |
(-40~250)℃ |
||
MRD9002T |
(-40~250)℃ |
||
MRD9003 |
(-40~250)℃ |
||
MRD9004 |
(-40~250)℃ |
||
MRD9005 |
(-40~250)℃ |
||
MRD9006 |
(-40~200)℃ |
||
Relative humidity |
˂ 95% |
||
Pressure |
Max. 4MPa |
||
Vibration |
Mechanical vibration 10m/s² , (10~150)Hz |
Installation requirements

Mount at 1/4 or 1/6 of the diameter.
Note: The minimum distance from the tank wall should be 200mm.
Note: ① Datum plane; ② Container center or symmetry axis
The top of the conical tank is flat and can be installed in the middle of the top of the tank to ensure that the measurement to the bottom of the cone is guaranteed.
When there is a material pile, the antenna should be vertically aligned with the material surface. If the material surface is not flat and the pile angle is large, a universal flange must be used to adjust the angle of the horn so that the horn can be aligned with the material surface as much as possible. (Due to the problem of echo attenuation and even loss of signal due to the inclined solid surface)